- Details:
-
The series also features 0.1 meters and full-degree amendment, cold-compensation, digital filtering, sensor fault processing, communications interface, 60 of the broken line input amendment process control, switching of input, output, and so on to switch function.
Selection:
61MXM808 standard self-tuning PID control instrumentation experts
60MXM908 enhanced self-tuning PID control instrumentation experts
60MXM808P standard curves in paragraph 50 programmable PID control instrumentation
60MXM908P enhanced 50 of the curve programmable PID control instrumentation
Technical parameters:
Input specifications: thermocouple: K, S, E, J, T, B, N, etc..
Thermal Resistance: Pt100, such as Cu50.
Resistance: 0 ~ 80 Ω, such as 0 to 400Ω.
Voltage: 0 ~ 20 mV…… 0 to 1V → input impedance ≥ 5 M Ω, 0 ~ 5V → input impedance ≥ 100 K Ω.
Current: 4 ~ 20 mA, 0 ~ 20mA, and other → input resistance ≤ 250 Ω 0 ~ 10mA → input resistance ≤ 500 Ω.
Expansion Specifications: in the above-mentioned reservations on the basis of input specifications, allows users to designate an additional input specifications (to provide a breakdown of the table). At this point Sn = 10
Measurement Range: -1999 ~ +9999.
Measurement accuracy: 0.2 (thermal resistance, voltage, current and copper thermocouple input resistance and compensation or compensation freezing cold end) 0.2% FS ± 2.0 ℃ (thermocouple input and internal components used instrument cold-temperature compensation )
Note: Instrumentation on the degree of B-thermocouple in the range 0 to 600 ℃ can be measured, but the measurement accuracy unattainable 0.2, in the range of 600 ~ 1800 ℃ guaranteed 0.2 measurement precision.
Response time: ≤ 0.5 seconds
Alarm features: maximum limit is deviation, such as four kinds of negative deviation, maximum output 3 Road, the police can choose from the power function.
Alarm output: relay contact switch output (normally open + normally closed), capacity of 220 contacts VAC/2A or 24 VDC/2A.
Alarm accuracy: ± 1 ± 1 ℃ or definition units.
Control output specifications: Relay: contact switch output (normally open + normally closed), capacity of 220 contacts VAC/2A or 24 VDC/2A.
SSR: driving voltage of 12 VDC/30mA (solid-state relay to drive SSR).
SCR: single-phase / three-phase zero (random) trigger, trigger 5 ~ 500 A of the duplex SCR, and two anti-parallel single-phase thyristor power modules connected or SCR.
Voltage: 0 to 5 V, 1 ~ 5V.
Current: 0-10 mA, 4 ~ 20mA, 0 ~ 20mA, etc.
Transmission range: 0 ~ 22mA, 0 ~ 10VDC transmission accuracy: 0.3 (± 0.3% FS)
Communications interfaces: RS485 serial communication interface, RS232C serial communication interface
Distribution output: 24 VDC voltage, maximum output current of 30 mA for the use of passive transmitter
Temperature Compensation: 0 ~ 50 ℃ Digital automatic temperature compensation.
Use of the environment: environmental temperature 0 to 50 ℃ ≤ 85% relative humidity, avoid strong corrosive gas
Power: Switching Power Supply 100 ~ 240 VAC (50HZ/60HZ), 24VDC ± 2V
Power: 5 W ≤
Weight: ≤ 1,000 g